TEL:021-3152 3588    Join Now   Sign In   Cart -  中文
Product Name : SY48K48H-PDNB
Item# : 192710-857
Model : 192710-857
Was Price: CNY0/pcs
Now Price : CNY0/pcs
Last update : 2018.10.23
Manufacturer :
More Picture:

 Symmetra PX 48kW All-in-One, without Batteries, 400V

Scalable power and distribution in a high-density, single-frame design. This high-efficiency 3-phase UPS scales as your data center grows up to 48kW/48kVA. Suitable for small & medium data center applications. To be used with either external third party battery system, or with internal long life modular batteries SYBT9-B4LL.

Includes: Network Management Card , Start-Up Service

 

SY48K48H-PDNB Features

Symmetra PX 48kW All-in-One, without Batteries, 400V

  • Dual mains input
    Increases availability by allowing the UPS to be connected to two separate power sources.

Symmetra PX Features & Benefits

Marketing Features
  • User-replaceable batteries
    Increases availability by allowing a trained user to perform upgrades and replacements of the batteries reducing Mean Time to Repair (MTTR)
  • User-replaceable power modules
    Enables simple upgrades and replacements of the Power Modules.
  • Modular design
    Provides fast serviceability and reduced maintenance requirements via self-diagnosing, field-replaceable modules.
  • Scalable power capacity
    Reduces UPS over-sizing costs today by allowing quick power upgrades, within the same footprint, later.
  • Power Modules connected in parallel
    Enhances availability by allowing immediate, seamless recovery from isolated module failures.
  • Battery modules connected in parallel
    Delivers higher availability through redundant batteries.
  • Configurable for N+1 internal redundancy
    Provides high availability through redundancy by allowing configuration with one more Power Module than is necessary to support the connected load.
  • Network manageable
    Provides remote power management of the UPS over the network.
  • Fully-rated power kVA equals kW
    Reduces cost by eliminating the need for an oversized UPS for Power Factor Corrected (PFC) loads.
  • Generator compatible
    Ensures clean, uninterrupted power to protected equipment when generator power is used.
Availability
  • Network manageable
    Provides remote power management of the UPS over the network.
  • Redundant Intelligence Modules
    Provides higher availability to the UPS connected loads by giving redundant communication paths to critical UPS functions.
  • Power Modules connected in parallel
    Enhances availability by allowing immediate, seamless recovery from isolated module failures.
  • Swappable power modules
    Allows quick addition of power capacity or replacement of existing power modules. Installed modules are automatically recognized by the system.
  • Modular design
    Provides fast serviceability and reduced maintenance requirements via self-diagnosing, field-replaceable modules.
  • Configurable for N+1 internal redundancy
    Provides high availability through redundancy by allowing configuration with one more Power Module than is necessary to support the connected load.
  • Automatic internal bypass
    Supplies utility power to the connected loads in the event of a UPS power overload or fault.
Sustainability
  • ENERGY STAR for UPS
    Establishes that the efficiency of the UPS is in the top 25% of the market as verified by third party testing
  • EU CoC for UPS
    Ensures that UPSs sold in the EU are highly efficient
Agility
  • Scalable power capacity
    Reduces UPS over-sizing costs today by allowing quick power upgrades, within the same footprint, later.
  • Programmable frequency
    Ensures compatibility with different input frequencies.
  • SmartSlot
    Customize UPS capabilities with management cards.
Manageability
  • Integrates with StruxureWare Data Center Expert
    An IT-ready, scalable access monitoring system that collects, organizes, and distributes critical alerts, surveillance video and key information, providing a unified view of complex physical infrastructure environments from anywhere on the network
  • LED status indicators
    Quickly understand unit and power status with visual indicators.
  • Audible alarms
    Provides notification of changing utility power and UPS power conditions
Total Cost of Ownership
  • Fully-rated power kVA equals kW
    Reduces cost by eliminating the need for an oversized UPS for Power Factor Corrected (PFC) loads.
  • Input power factor correction
    Minimizes installation costs by enabling the use of smaller generators and cabling.
  • Generator compatible
    Ensures clean, uninterrupted power to protected equipment when generator power is used.
  • 5x8 Start-up service included
    Required for full coverage of factory warranty

    Output

    • Output power capacity
      48.0 KWatts / 48.0 kVA
    • Max Configurable Power (Watts)
      48.0 KWatts / 48.0 kVA
    • Nominal Output Voltage
      230V , 400V 3PH
    • Output Voltage Note
      Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage
    • Output Voltage Distortion
      Less than 2%
    • Output Frequency (sync to mains)
      50/60 Hz +/- 3 Hz user adjustable +/- 0.1
    • Output Frequency (not synced)
      60Hz +/- 0.1% for 60Hz nominal, 50Hz +/- 0.1% for 50Hz nominal
    • Other Output Voltages
      380, 400, 415
    • Topology
      Double Conversion Online
    • Waveform type
      Sine wave
    • Overload Operation
      10 minutes @ 125% and 60 seconds @ 150%
    • Output Voltage THD
      < 2% for 0 to 100% linear load and < 6% for full non linear load
    • Output Voltage Tolerance
      +/-1% static and +/- 5% at 100% load step
    • Bypass
      Built-in Static Bypass

    Input

    • Nominal Input Voltage
      400V 3PH
    • Input frequency
      40 - 70 Hz
    • Input Connections
      Hard Wire 5-wire (3PH + N + G)
    • Input voltage range for main operations
      340 - 477V
    • Input Total Harmonic Distortion
      Less than 5% for full load
    • Type of Input Protection Required
      gL fuse
    • Other Input Voltages
      380, 400, 415
    • Maximum Short Circuit Withstand (Icw)
      30.0kAmps
    • Maximum Input Current
      98.0A
    • Input Power Factor at Full Load
      0.99

    Batteries & Runtime

    • Battery type
      No internal battery - uses external battery system

    Communications & Management

    • Interface Port(s)
      DB-9 RS-232 , SmartSlot
    • Control panel
      Multi-function LCD status and control console
    • Audible Alarm
      Audible and visible alarms : configurable delays
    • Emergency Power Off (EPO)
      Yes
    • Available SmartSlot™ Interface Quantity
      2

    Physical

    • Maximum Height
      1991mm , 199.1CM
    • Maximum Width
      600mm , 60.0CM
    • Maximum Depth
      1070mm , 107.0CM
    • Net Weight
      397.0KG
    • Shipping weight
      430.0KG
    • Shipping Height
      2140mm , 214.0CM
    • Shipping Width
      848mm , 84.8CM
    • Shipping Depth
      1210mm , 121.0CM

    Environmental

    • Operating Temperature
      0 - 40 °C
    • Operating Relative Humidity
      0 - 95 %
    • Operating Elevation
      0-999.9meters
    • Storage Temperature
      -15 - 40 °C
    • Storage Relative Humidity
      0 - 95 %
    • Storage Elevation
      0-15000meters
    • Audible noise at 1 meter from surface of unit
      61.0dBA
    • Online thermal dissipation
      7719.0BTU/hr
    • Protection Class
      NEMA 1

    Conformance

    • Approvals
      EN 50091-1, EN/IEC 62040-1, EN/IEC 62040-2, EN/IEC 62040-3, ISO 14001, ISO 9001, VFI-SS-111
    • Standard warranty
      1 year on-site repair or replace with factory authorized Start-Up

    General

    • Bypass Connection
      5 wire (3PH + N + G)
    • Bypass Protection Device
      80.0
    • Max Bypass Input Current
      80.0A

 

| Clicks:

Online Server

Salesperson①
Salesperson②
Salesperson③
Engineer
Customer service